AC Sources in a Circuit

Most electrical equipment onboard are powered by Alternating Current. Main Switchboards, Pumps, Lighting, Galley and Thrusters will all be powered by AC. There may be some instances where Direct Current will be used (Batteries, Control Circuits and Emergency Systems), however the main equipment will be powered by AC. It is important to understand what an AC source is, how they work in a circuit and why they are different from batteries.

Want to understand AC sources and electrical circuits in practical shipboard applications? Explore the Electrical Circuit Diagram Course by Merchant Navy Decoded to strengthen your electrical knowledge.

What is Alternating Current?

AC Sources In A Circuit

Unlike DC, AC has a voltage and current that will continuously change directions. If we plotted this onto a graph over time, we would see a nice clean sine wave. The voltage will go up to a peak, then down to zero, then become negative to a peak.

Key Terms:

  • Frequency – The number of complete cycles per second. Measured in Hertz (Hz). The majority of ships will be 60Hz however some may be 50Hz. One cycle would take around 16.7ms.
  • Peak Value – The maximum voltage achieved in either direction.
  • RMS Value – The effective value of the voltage. Gives the same amount of heating effect as a DC supply of the same value. When a ship is said to have a 440V supply, this value is the RMS value. The voltmeters on the switchboard will show an RMS value.
  • Phase – Indicates what point on the wave the voltage is at. Measured in Degrees. 360 Degrees = 1 Cycle.

With Sine Waves the Peak Value can be calculated by multiplying the RMS value by √2 (approximately 1.414). If our RMS value was 440V our actual Peak Voltage would be approximately 622V. Our insulation and equipment must be rated to cope with this.

AC Sources On Board

An AC source is any piece of equipment that can provide an Alternating Voltage to a load. Typical AC sources on board include:

  • Main Generators (Alternators) – These use a diesel or Turbine Engine to spin a rotor. This causes an Alternating Voltage to be produced in the Stator Windings. This is the main source of Alternating Voltage. The frequency will depend on the speed of rotation of the rotor and number of poles on the generator. The voltage will depend on the level of excitation and will be controlled by the Automatic Voltage Regulator (AVR).

Main Generators

  • Emergency Generator – Works on the same principles.

Emergency Generator

  • Shaft Generator – Alternator powered by the Main Engine/Gearbox.
  • Shore Supply – This is the AC supply provided by the port. The voltage and frequency must match that of the ship however can be converted.

Shore Supply

  • Transformer Secondary – Transformers do not provide any power however they can convert an AC voltage of one rating to another. From the loads point of view this will appear as an AC source. Example would be a 440V to 220V Transformer for lighting.
  • Inverters & UPS Units – Convert the DC voltage from the batteries to an AC supply to power critical equipment such as navigation and control systems.

Table of Contents

AC Source In A Circuit

reality all AC sources will have some form of internal impedance. This is due to the resistance and reactance of the windings. As the current flows through this impedance there will be a voltage drop. Therefore as the load increases, the voltage at the terminals will reduce.

When a large motor is started there will be a voltage drop on the generators. The AVR will constantly try to increase the excitation to keep a stable voltage. If a generator becomes overloaded there will be a low voltage and low frequency. Resistors, Inductors & Capacitors will all affect the behaviour of the circuit. Real equipment usually consists of all 3.

Resistive

Heaters, Incandescent Lamps, Galley Elements. The current and voltage will increase and decrease together. They will be in phase. All power will be used for useful work.

Inductive

Motors, Transformers, Fluorescent Lamp Ballasts. These have coils. Coils resist changes in current so the current will lag behind. This is known as Inductive Reactance. Can be calculated using XL = 2Ï€fL. Frequency will cause this to increase.

Capacitive

Capacitors (Power Factor Correction Banks & some electronic equipment). This will cause current to lead. This resistance is known as Capacitive Reactance. Can be calculated using XC = 1/(2Ï€fC). Frequency will cause this to decrease.

Impedance (Z) is the total resistance to an Alternating Current. Made up of Resistance & Reactance.

Real, Reactive & Apparent Power

There may be a phase difference between the voltage and current. This means there are 3 types of power.

  • Real Power (P) – Measured in kW. This is useful power such as turning a shaft.
  • Reactive Power (Q) – Measured in kVAr. This is constantly changing power. Used to create the magnetic & electric fields in motors, transformers & capacitors. This is not useful however it will cause loading.
  • Apparent Power (S) – Measured in kVA. This combines both powers. This is what the generator and cables need to be able to handle.

The ratio of Real Power to Apparent Power is known as the Power Factor (Cos φ). If the Power Factor is 1 then all the current is being used for useful work. If the Power Factor is low then a greater current will be required to achieve the same amount of useful power. Generators are rated in kVA. They will have a set Power Factor (usually 0.8). If a generator is rated at 100kVA with a Power Factor of 0.8 it can only provide 80kW of Real Power.

A low Power Factor (usually caused by underloaded motors) will cause more capacity to be used by the generator and cause the cables to heat up. This is why generators will share their load based upon kW & kVAr. The AVRs are important here.

Single & Three Phase

  • Single Phase – Provides 1 Alternating Voltage. Used for lighting, small appliances and sockets (220V).
  • Three Phase – Provides 3 Alternating Voltages. This is how the main power is generated and distributed on board. This provides a smooth and efficient power supply. Less Copper is required to provide the same amount of power. Three Phase motors can self start and run due to a rotating magnetic field.

Three Phase windings can be configured as Star or Delta. With Star there are 2 voltages to consider.

  1. Line Voltage – Voltage between 2 phases.
  2. Phase Voltage – Voltage between a phase and the star point.

With a star connection:-

Line Voltage = √3 x Phase Voltage

If the system is 440V then the phase voltage will be 440 / 1.732 = 254V. The 220V lighting is a separate system and will be provided via a transformer.

Power in a balanced Three Phase Load can be calculated using:-

P = √3 x V(line) x I(line) x Cos φ

Example: Three Phase Motor supplied with 440V and drawing 100A. Power Factor of 0.8.

Apparent Power = 1.732 x 440 x 100 = 76,208VA = 76.2kVA

Real Power = 76.2kVA x 0.8 = 61kW

Why AC Is Used On Ships

  1. Transformers can be used with AC. The voltage can easily be changed. This allows high voltage to be used for distribution and low voltage for the load.
  2. Generators are simple and robust. They do not have a commutator or brushes to carry the main current.
  3. Motors (especially squirrel cage induction motors) are robust, cost effective and require little maintenance. This is suitable for pumps, fans & compressors.
  4. Three Phase is efficient and provides smooth torque.
  5. Protection & switching is easy. As the current drops to 0 twice per cycle it is easier for the circuit breaker to open.

Matching Sources – Paralleling

Before connecting any AC sources (generators, generators & shore supply) together they need to be matched. The incoming source needs to be of the same voltage, frequency & phase as the live busbar. They also need to have the same phase sequence. This can be done using a Synchroscope or Synchronising Lamps. If the breaker is not in sync when closing it will cause a large surge of current. This can cause a mechanical impact on the generator.

Once the sources have been paralleled they will share the load. Real Power will be shared using the engine governors. Reactive Power will be shared using the AVRs.

Best Practice

  • Remember the meter will display an RMS value. Equipment must be rated to cope with the peak.
  • Take notice of kW & kVAr when paralleling.
  • Ensure the AVRs & Governors are in good condition. Check the settings after repairs.
  • Never close a breaker onto the bus unless it is properly in sync.
  • Ensure single phase loads are split evenly.
  • Be careful with shore connections. Ensure the voltage, frequency & phase sequence are correct.
  • Always follow isolation & lock off procedures. Prove dead before working on any AC circuits.

Conclusion

An AC Source is not just an alternating battery. It has a frequency, phase, internal impedance & power factor. All these will affect how it will behave in a circuit. Generators, Transformers, Shore supply and Inverters all provide the same basic function of providing Alternating Voltage to a load. If you understand RMS/Peak, Resistance/Reactance, kW/kVA & Line/Phase Voltage then most meters on the switchboard will be easy to read.

Frequently Asked Questions (FAQs)

Any piece of equipment that provides an Alternating Voltage to a circuit. This could be a Generator, Shaft Generator, Shore Supply, Transformer Secondary or Inverter.

This means the Line Voltage between the phases (RMS). The Peak Voltage will be higher. 440 x 1.414 = 622V.

Line Voltage is between 2 phases. Phase Voltage is between a phase and a star point. If the winding is in a Star configuration the Line Voltage will be √3 times larger than the Phase Voltage. In a 440V system the Phase Voltage will be approximately 254V.

The ratio of Real Power (kW) to Apparent Power (kVA). A low Power Factor means more current will be required.

kW – Real Power. Useful Power. kVAr – Reactive Power. Used to create magnetic & electric fields. kVA – Apparent Power. Combines both kW & kVAr. This is what the generator and cables need to be able to handle.

There will be a voltage drop across the internal impedance. The engine will slow down due to the overload.

Voltage, Frequency, Phase & Phase Sequence.



It is efficient, uses less copper and provides a smooth power. Three Phase Motors are robust and can be easily run. Transformers can be used to easily change the voltage.

Disclaimer :- The opinions expressed in this article belong solely to the author and may not necessarily reflect those of Merchant Navy Decoded. We cannot guarantee the accuracy of the information provided and disclaim any responsibility for it. Data and visuals used are sourced from publicly available information and may not be authenticated by any regulatory body. Reviews and comments appearing on our blogs represent the opinions of individuals and do not necessarily reflect the views of Merchant Navy Decoded. We are not responsible for any loss or damage resulting from reliance on these reviews or comments.

Reproduction, copying, sharing, or use of the article or images in any form is strictly prohibited without prior permission from both the author and Merchant Navy Decoded.

DIWALI SALE

Decoded Discount Alert! up to 50% OFF

DIWALI SALE

Decoded Discount Alert! up to 50% OFF

Use Coupon Code Deep50

Days
Hours
Seconds
0
Would love your thoughts, please comment.x
()
x